Elettra-Sincrotrone Trieste S.C.p.A. website uses session cookies which are required for users to navigate appropriately and safely. Session cookies created by the Elettra-Sincrotrone Trieste S.C.p.A. website navigation do not affect users' privacy during their browsing experience on our website, as they do not entail processing their personal identification data. Session cookies are not permanently stored and indeed are cancelled when the connection to the Elettra-Sincrotrone Trieste S.C.p.A. website is terminated.
More info
OK

VACO controllers troubleshooting

Pneumatic valve opens/closes randomly when VACO controller is in local mode
While it works well in remote, it does not respond in local (this happened for instance for V-PC3A).

The problem is most likely in the corresponding VACO controller card.
The problem was associated with a mulfunctioning of the push button, which contacts need to be cleaned (Andrea Martin) or the whole push button must be replaced.
Ref. Persons: Christian Amasoli (Laboratorio controlli,  where a testing station for the VACO cards is situated) and Igor Píš

How to exchange a VACO controller card

  1. Switch the VACO controller to Local mode.
  2. Switch-off  the VACO controller and wait a couple of seconds (cca 1/2 minute).
  3. Exchange the VACO cards.
  4. Switch-on the VACO controller.
  5. Switch the VACO controller to Remote mode.